PAX, Digital Display Meter
- Digital Display Indicator
- Analog or Frequency Input
- Range of Mathematic Functions
- Protection Class: IP65
- RS-232/485 Interface (Option)
- Analog Outputs (Option)
- Relay Outputs (Option)
- Linearization of up to 16 Steps
The device is programmed either by PC or by 5 keys, directly. Additional functions e.g. Minimum-Maximum memory, tare, delete memory….., can be performed by keys or 3 programmable inputs. The programmable inputs can be adjusted by jumpers PNP- or NPN.
For PAXD and PAXS a linearization of up to 16 steps is possible. In addition, PAXD and PAXS include a summation counter. Both device have an easy to be changed backlit physical unit display. PAXD processes a wide range of DC voltage-, DC current- and resistance signals. The range is being adjusted by jumpers and in the programming. Thus, the unit is especially applicable for sensors with active output signals.
PAXS processes input signals in the range of ±24 mV DC (dissolution 1 µV) or ±240 mV DC (dissolution 10 µV) and is mainly used with passive sensors. PAXI is a counter-tachometer unit. It processes impulses in the range of 0.01 Hz up to 34 kHz. Input signals of NPN-, PNP-sensors, CMOS, TTL, potential-free contacts and permanent magnetic sensors can be processed. The device has 3 counters and a tachometer which are scaleable independently from each other.
The decimal point can be selected freely. By a rounding factor and digital filtration the display is being soothed if necessary.
The device can be equipped, or at a later time upgraded, with various output cards. At the Max., the device can be provided
with each one limit value- , an analog output- and an interface slot.
Each PAX unit is also available as a LPAX-model. LPAX has a large display (38 mm height LED-unit) which is legible from a distance of 20 m. LPAX can be delivered either as an assembly kit or already mounted in a 28 TE-table housing. (See PAX-TG data sheet).
Input Type | DC Voltage |
DC Current | |
No. of Inputs | 1 |
Excitation | 10 V DC |
12 V DC | |
24 V DC | |
Output Type | DC Voltage |
DC Current | |
Relay | |
Interface | RS-232/485 |
Supply Power | 11 - 36 V DC |
85 - 250 V AC | |
IP Rating | IP65 |
PAXD0000 | Voltage/Current Input, 85-250 VAC Supply Voltage |
PAXD0010 | Voltage/Current Input, 11-36 VDC Supply Voltage |
PAXS0000 | Passive Sensor Input, 85-250 VAC Supply Voltage |
PAXS0010 | Passive Sensor Input, 11-36 VDC Supply Voltage |
PAXI0000 | Frequency Input, 85-250 VAC Supply Voltage |
PAXI0010 | Frequency Input, 11-36 VDC Supply Voltage |
PAX, Digital Built-In Measuring Device Datasheet |
- Panel Mount Indicator
- DC Voltage Analog Inputs
- Protection Class: IP65
- RS-232/485 or BCD Interface (Option)
- Isolated Relay Output (Option)
- Isolated Analog Output (Option)
- Low AC/DC Power Supply (Option)
- Overvoltage Protection
Input Type | DC Voltage |
No. of Inputs | 1 |
Excitation | 5 V DC, 10 V DC, 24 V DC |
Output Type | DC Voltage, DC Current, Relay |
Interface | RS-232/485 |
Supply Power | 9 - 32 V DC, 8 - 28 V AC, 85 - 250 V AC |
- Panel Mount Indicator
- DC Current Analog Inputs
- Protection Class: IP65
- RS-232/485 or BCD Interface (Option)
- Isolated Relay Output (Option)
- Isolated Analog Output (Option)
- Low AC/DC Power Supply (Option)
- Overcurrent Protection
Input Type | DC Current |
No. of Inputs | 1 |
Excitation | 5 V DC, 10 V DC, 24 V DC |
Output Type | DC Voltage, DC Current, Relay |
Interface | RS-232/485 |
Supply Power | 9 - 32 V DC, 8 - 28 V AC, 85 - 250 V AC |
- Panel Mount Indicator
- Process Signal Inputs
- Protection Class: IP65
- Custom Scaling (Model 2162X)
- RS-232/485 Interface (Option)
- Isolated Relay Output (Option)
- Isolated Analog Output (Option)
- Low AC/DC Power Supply (Option)
Input Type | DC Current |
No. of Inputs | 1 |
Excitation | 5 V DC, 10 V DC, 24 V DC |
Output Type | DC Voltage, DC Current, Relay |
Interface | RS-232/485 |
Supply Power | 9 - 32 V DC, 8 - 28 V AC, 85 - 250 V AC |
- Panel Mount Indicator
- Strain Gauge Analog Inputs
- Protection Class: IP65
- Custom Scaling (Model 2170X)
- RS-232/485 Interface (Option)
- Isolated Relay Output (Option)
- Isolated Analog Output (Option)
- Low AC/DC Power Supply (Option)
Input Type | DC Voltage, Strain Gauge |
No. of Inputs | 1 |
Excitation | 5 V DC, 10 V DC, 24 V DC |
Output Type | DC Voltage, DC Current, Relay |
Interface | RS-232/485 |
Supply Power | 9 - 32 V DC, 8 - 28 V AC, 85 - 250 V AC |
- Panel Mount Indicator
- Quadrature Encoder Inputs
- Protection Class: IP65
- RS-232/485 Interface (Option)
- Isolated Relay Output (Option)
- Isolated Analog Output (Option)
- Low AC/DC Power Supply (Option)
- Overvoltage Protection
Input Type | Encoder |
No. of Inputs | 1 |
Excitation | 5 V DC, 10 V DC, 24 V DC |
Output Type | DC Voltage, DC Current, Relay |
Interface | RS-232/485 |
Supply Power | 9 - 32 V DC, 8 - 28 V AC, 85 - 250 V AC |