Loading...
A-Tech Instruments Ltd.
Français   |   Welcome. Please Register an Account or Login

SCM5B31, Voltage Input Analog Modular Signal Conditioner

The SCM5B31 voltage input module provides a single channel of analog input which is filtered, isolated, amplified and converted to a high-level voltage output. These modules can share a common analog bus with external multiplexers.
SCM5B31, Voltage Input Analog Modular Signal Conditioner
SCM5B31, Voltage Input Analog Modular Signal Conditioner
Features:
  • Narrow Bandwidth Voltage Input Module
  • 1500 V Transformer Isolation
  • Accuracy: ± 0.03%
  • Module
  • ANSI/IEEE C37.90.1 Transient Protection
  • Input Protected to 240 V AC Continuous
Manufacturer:  Dataforth
Quote
Datasheet
Specifications
Models & Accessories
Downloads
Similar Products
SCM5B31 - Specifications
FamilyDataforth 5B
Input Type±1 V DC
±5 V DC
±10 V DC
±20 V DC
±40 V DC
# of Inputs1
Output Type0 - 5 V DC
0 - 10 V DC
±5 V DC
±10 V DC
Bandwidth4 Hz
IsolationYes
Supply Power5 V DC
SCM5B31 - Models & Accessories
Models
SCM5B31-01± 1 V Input, ± 5 V DC Output
SCM5B31-01D± 1 V Input, ± 10 V DC Output
SCM5B31-02± 5 V Input, ± 5 V DC Output
SCM5B31-02D± 5 V Input, ± 10 V DC Output
SCM5B31-03± 10 V Input, ± 5 V DC Output
SCM5B31-03D± 10 V Input, ± 10 V DC Output
SCM5B31-04± 1 V Input, 0-5 V DC Output
SCM5B31-04D± 1 V Input, 0-10 V DC Output
SCM5B31-05± 5 V Input, 0-5 V DC Output
SCM5B31-05D± 5 V Input, 0-10 V DC Output
SCM5B31-06± 10 V Input, 0-5 V DC Output
SCM5B31-06D± 10 V Input, 0-10 V DC Output
SCM5B31-07± 20 V Input, ± 5 V DC Output
SCM5B31-07D± 20 V Input, ± 10 V DC Output
SCM5B31-08± 20 V Input, 0-5 V DC Output
SCM5B31-08D± 20 V Input, 0-10 V DC Output
SCM5B31-09± 40 V Input, ± 5 V DC Output
SCM5B31-09D ± 40 V Input, ± 10 V DC Output
SCM5B31-10± 40 V Input, 0-5 V DC Output
SCM5B31-10D± 40 V Input, 0-10 V DC Output
SCM5B31 - Downloads
SCM5B31 - Similar Products
  • Narrow Bandwidth Voltage Input Module
  • 1500 V Transformer Isolation
  • Accuracy: ± 0.03%
  • Module
  • ANSI/IEEE C37.90.1 Transient Protection
  • Input Protected to 240 V AC Continuous
Family
Dataforth 5B
Input Type
±10 mV DC,
±50 mV DC,
±100 mV DC,
±1 V DC
# of Inputs
1
Output Type
0 - 5 V DC,
0 - 10 V DC,
±5 V DC,
±10 V DC
Bandwidth
4 Hz
Isolation
Yes
  • Accepts Millivolt and Voltage Level Signals
  • High-Level Voltage Outputs
  • Voltage Input Module
  • 1500 V Transformer Isolation
  • Accuracy: ± 0.05%
  • ANSI/IEEE C37.90.1 Transient Protection
  • Input Protected to 240 V AC Continuous
Family
Dataforth 8B
Input Type
±10 mV DC,
±50 mV DC,
±100 mV DC
# of Inputs
1
Output Type
0 - 5 V DC,
±5 V DC
Bandwidth
3 Hz
Isolation
Yes
  • Strain Gauge Input Module
  • 1500 V Transformer Isolation
  • Accuracy: ± 0.05%
  • Module
  • ANSI/IEEE C37.90.1 Transient Protection
  • Input Protected to 240 V AC Continuous
Family
Dataforth 8B
Input Type
±10 mV DC,
±20 mV DC,
±30 mV DC,
Strain Gauge
# of Inputs
1
Output Type
0 - 5 V DC,
±5 V DC
Bandwidth
3 Hz,
8 kHz
Excitation
3.33 V DC,
10 V DC
  • Voltage Input Module
  • 1500 V Transformer Isolation
  • Accuracy: ± 0.05%
  • Module
  • ANSI/IEEE C37.90.1 Transient Protection
  • Input Protected to 240 V AC Continuous
Family
Dataforth 8B
Input Type
±1 V DC,
±5 V DC,
±10 V DC,
±20 V DC,
±40 V DC,
±60 V DC
# of Inputs
1
Output Type
0 - 5 V DC,
±5 V DC
Bandwidth
3 Hz
Isolation
Yes
  • Voltage Output Module
  • 1500 V Transformer Isolation
  • Accuracy: ±0.03%
  • Module
  • ANSI/IEEE C37.90.1 Transient Protection
  • Track & Hold Circuit
Family
Dataforth 5B
Input Type
0 - 5 V DC,
0 - 10 V DC,
±5 V DC,
±10 V DC
# of Inputs
1
Output Type
0 - 5 V DC,
0 - 10 V DC,
±5 V DC,
±10 V DC
Bandwidth
400 Hz
Isolation
Yes
Products    |    Applications    |    Services    |    Partners    |    About Us    |    Contact Us
© A-Tech Instruments Ltd.