SCM5B47, Thermocouple Input Analog Modular Signal Conditioner
- Linearized Thermocouple Input Module
- 1500 V Transformer Isolation
- Accuracy: ± 0.07% to ± 0.16%
- Module
- ANSI/IEEE C37.90.1 Transient Protection
- Input Protected to 240 V AC Continuous
Family | Dataforth 5B |
Input Type | Thermocouple |
# of Inputs | 1 |
Output Type | 0 - 5 V DC |
0 - 10 V DC | |
Bandwidth | 4 Hz |
Isolation | Yes |
Supply Power | 5 V DC |
SCM5B47J-01 | J-Type Thermocouple, 0 to 760°C Input, 0-5 V DC Output |
SCM5B47J-02 | J-Type Thermocouple, -100 to 300°C Input, 0-5 V DC Output |
SCM5B47J-03 | J-Type Thermocouple, 0 to 500°C Input, 0-5 V DC Output |
SCM5B47K-04 | K-Type Thermocouple, 0 to 1000°C Input, 0-5 V DC Output |
SCM5B47K-05 | K-Type Thermocouple, 0 to 500°C Input, 0-5 V DC Output |
SCM5B47T-06 | T-Type Thermocouple, -100 to 400°C Input, 0-5 V DC Output |
SCM5B47T-07 | T-Type Thermocouple, 0 to 200°C Input, 0-5 V DC Output |
SCM5B47E-08 | E-Type Thermocouple, 0 to 1000°C Input, 0-5 V DC Output |
SCM5B47R-09 | R-Type Thermocouple, 500 to 1750°C Input, 0-5 V DC Output |
SCM5B47S-10 | S-Type Thermocouple, 500 to 1750°C Input, 0-5 V DC Output |
SCM5B47B-11 | B-Type Thermocouple, 500 to 1800°C Input, 0-5 V DC Output |
SCM5B47J-12 | J-Type Thermocouple, -100 to 760°C Input, 0-5 V DC Output |
SCM5B47K-13 | K-Type Thermocouple, -100 to 1350°C Input, 0-5 V DC Output |
SCM5B47K-14 | K-Type Thermocouple, 0 to 1200°C Input, 0-5 V DC Output |
SCM5B47N-15 | N-Type Thermocouple, -100 to 1300°C Input, 0-5 V DC Output |
SCM5B47J-01D | J-Type Thermocouple, 0 to 760°C Input, 0-10 V DC Output |
SCM5B47J-02D | J-Type Thermocouple, -100 to 300°C Input, 0-10 V DC Output |
SCM5B47J-03D | J-Type Thermocouple, 0 to 500°C Input, 0-10 V DC Output |
SCM5B47K-04D | K-Type Thermocouple, 0 to 1000°C Input, 0-10 V DC Output |
SCM5B47K-05D | K-Type Thermocouple, 0 to 500°C Input, 0-10 V DC Output |
SCM5B47T-06D | T-Type Thermocouple, -100 to 400°C Input, 0-10 V DC Output |
SCM5B47T-07D | T-Type Thermocouple, 0 to 200°C Input, 0-10 V DC Output |
SCM5B47E-08D | E-Type Thermocouple, 0 to 1000°C Input, 0-10 V DC Output |
SCM5B47R-09D | R-Type Thermocouple, 500 to 1750°C Input, 0-10 V DC Output |
SCM5B47S-10D | S-Type Thermocouple, 500 to 1750°C Input, 0-10 V DC Output |
SCM5B47B-11D | B-Type Thermocouple, 500 to 1800°C Input, 0-10 V DC Output |
SCM5B47J-12D | J-Type Thermocouple, 0 to 760°C Input, 0-10 V DC Output |
SCM5B47K-13D | K-Type Thermocouple, -100 to 1350°C Input, 0-10 V DC Output |
SCM5B47K-14D | K-Type Thermocouple, 0 to 1200°C Input, 0-10 V DC Output |
SCM5B47N-15D | T-Type Thermocouple, -100 to 1300°C Input, 0-10 V DC Output |
SCM5B47 Datasheet |
AN101 RMS_Voltage_Current App Note |
AN121 RiseTime vs BW App Note |
AN126 Tuning_Surge_Tank_Level_Control_Loops App Note |
AN128 RMS Revisited App Note |
AN129 Harmonics and utility costs App Note |
Hysteresis Specifications Tech Note |
Faraday's Law of Induction Tech Note |
Data Acquisition Systems Accessories Tech Note |
Signal Conditioner Surge Withstand Capability Tech Note |
Signal-to-Noise Ratio, SNR Tech Note |
Signal Conditioning Measured vs Combinational Error Tech Note |
When Good Grounds Go Bad Tech Note |
Sample Test Report Tech Note |
Analog Signal Isolation and Protection Tech Note |
Why Should Sensors Be Isolated Tech Note |
- Linearized 2- or 3-Wire RTD Input Module
- 1500 V Transformer Isolation
- Accuracy: ± 0.06°C to ± 0.36°C
- Module
- ANSI/IEEE C37.90.1 Transient Protection
- Input Protected to 240 V AC Continuous
Family | Dataforth 5B |
Input Type | RTD |
# of Inputs | 1 |
Output Type | 0 - 5 V DC, 0 - 10 V DC |
Bandwidth | 4 Hz |
Isolation | Yes |
- Linearized 4-Wire RTD Input Module
- 1500 V Transformer Isolation
- Accuracy: ± 0.06°C to ± 0.36°C
- Module
- ANSI/IEEE C37.90.1 Transient Protection
- Input Protected to 240 V AC Continuous
Family | Dataforth 5B |
Input Type | RTD |
# of Inputs | 1 |
Output Type | 0 - 5 V DC, 0 - 10 V DC |
Bandwidth | 4 Hz |
Isolation | Yes |
- Non-Linearized Thermocouple Input Module
- 1500 V Transformer Isolation
- Accuracy: ± 0.03%
- Module
- ANSI/IEEE C37.90.1 Transient Protection
- Input Protected to 240 V AC Continuous
Family | Dataforth 5B |
Input Type | Thermocouple |
# of Inputs | 1 |
Output Type | 0 - 5 V DC, 0 - 10 V DC |
Bandwidth | 4 Hz |
Isolation | Yes |
- Linearized Thermocouple Input Module
- 1500 V Isolation
- Accuracy: ± 0.10% to ± 0.20%
- Module
- ANSI/IEEE C37.90.1 Transient Protection
- Input Protected to 240 V AC Continuous
Family | Dataforth 8B |
Input Type | Thermocouple |
# of Inputs | 1 |
Output Type | 0 - 5 V DC |
Bandwidth | 3 Hz |
Isolation | Yes |
- Narrow Bandwidth Voltage Input Module
- 1500 V Transformer Isolation
- Accuracy: ± 0.03%
- Module
- ANSI/IEEE C37.90.1 Transient Protection
- Input Protected to 240 V AC Continuous
Family | Dataforth 5B |
Input Type | ±10 mV DC, ±50 mV DC, ±100 mV DC, ±1 V DC |
# of Inputs | 1 |
Output Type | 0 - 5 V DC, 0 - 10 V DC, ±5 V DC, ±10 V DC |
Bandwidth | 4 Hz |
Isolation | Yes |