DSCT36, Potentiometer Input Transmitters
- Interfaces to Potentiometers up to 10 kOhm
- Process Current Output
- 1500Vrms Transformer Isolation
- ANSI/IEEE C37.90.1 Transient Protection
- Input and Output Protected to 240VAC Continuous
- Up to 60V Loop Voltage
- 160dB CMR
- 85dB NMR at 60Hz, 80dB at 50Hz
- ±0.03% Accuracy
- ±0.01% Linearity
- Easily Mounts on Standard DIN Rail
- CSA and FM Approvals Pending
- CE Compliant
Each DSCT36 potentiometer input transmitter provides a single channel of potentiometer input which is filtered, isolated, amplified, and converted to a process current output. Signal filtering is accomplished with a five-pole filter, which provides 85dB of normal-mode rejection at 60Hz and 80dB at 50Hz. An anti-aliasing pole is located on the field side of the isolation barrier, and the other four are on the process loop side. After the initial field-side filtering, the input signal is chopped by a proprietary chopper circuit. Isolation is provided by transformer coupling, again using a proprietary technique to suppress transmission of common mode spikes or surges.
Potentiometer excitation is provided from the transmitter using a precision current source. The excitation current is small (less than 0.26mA) which minimizes self-heating of the potentiometer. Lead compensation is achieved by matching two current paths which cancels the effects of lead resistance.
Special input and output circuits on the DSCT36 transmitters provide protection against accidental connection of power-line voltages up to 240VAC and against transient events as defined by ANSI/IEEE C37.90.1. Signal and loop power lines are secured to the module using screw terminals, which are in pluggable terminal blocks for ease of system assembly and reconfiguration.
The modules have excellent stability over time and do not require recalibration, however, zero and span settings are adjustable up to ±10% to accommodate situations where fine-tuning is desired. The adjustments are made using potentiometers located under the front panel label and are non-interactive for ease of use.
Input Type | Potentiometer |
# of Inputs | 1 |
Output Type | 4 - 20 mA |
Max Bandwidth | 3 Hz |
Isolation | Yes |
Supply Power | 12 - 60 V DC |
DSCT36-01 | 0 to 100Ω |
DSCT36-02 | 0 to 500Ω |
DSCT36-03 | 0 to 1000Ω |
DSCT36-04 | 0 to 10,000Ω |
DSCT36 Potentiometer Input Transmitter V2 Datasheet |
DSCT36, Potentiometer Input Transmitters Datasheet |
DSCT Diagram Drawings |
DSCT Intro Brochure |
AN101 RMS_Voltage_Current App Note |
AN105 Resistance Temperature Detector V2 App Note |
AN121 RiseTime vs BW App Note |
AN126 Tuning_Surge_Tank_Level_Control_Loops App Note |
AN127 OP-Amp Errors, another View App Note |
AN128 RMS Revisited App Note |
AN129 Harmonics and utility costs App Note |
Hysteresis Specifications Tech Note |
Faraday's Law of Induction Tech Note |
Data Acquisition Systems Accessories Tech Note |
Signal Conditioner Surge Withstand Capability Tech Note |
Signal-to-Noise Ratio, SNR Tech Note |
Signal Conditioning Measured vs Combinational Error Tech Note |
When Good Grounds Go Bad Tech Note |
Signal Conditioner Life Tech Note |
Why Should Sensors Be Isolated Tech Note |
- Potentiometer Input Module
- 1500 V Transformer Isolation
- True 3-Way Isolation
- Accuracy: ± 0.03%
- DIN Rail Mounted Module
- ANSI/IEEE C37.90.1 Transient Protection
- Input Protected to 240 V AC Continuous
Input Type | Potentiometer |
# of Inputs | 1 |
Output Type | 0 - 10 V DC, 0 - 20 mA, 4 - 20 mA |
Max Bandwidth | 3 Hz |
Isolation | Yes |
Supply Power | 15 - 30 V DC |
- Accepts Millivolt and Voltage Level Signals
- Process Current Output
- 1500Vrms Transformer Isolation
- ANSI/IEEE C37.90.1 Transient Protection
- Input and Output Protected to 240VAC Continuous
- Up to 60V Loop Voltage
- 160dB CMR
- 85dB NMR at 60Hz, 80dB at 50Hz
Input Type | 0 - 10 mV DC, 0 - 50 mV DC, 0 - 100 mV DC, 0 - 1 V DC, 0 - 5 V DC, 0 - 10 V DC, 0 - 20 V DC, ±10 mV DC, ±50 mV DC, ±100 mV DC, ±1 V DC, ±5 V DC, ±10 V DC, ±20 V DC |
# of Inputs | 1 |
Output Type | 4 - 20 mA |
Max Bandwidth | 3 Hz |
Isolation | Yes |
Supply Power | 12 - 60 V DC |
- Transmitter for Potentiometers
- Output 0 / 4…20 mA / 0…5 mA / 0…2 / 5 / 10 V / ±10 V
- Rate up to 7200 meas./s
- Teach-in, tare, linearization, and digital filters
- Configuration via DIP switch or PC software
- Galvanic isolation: 2.5 kVAC
- Power supply: 10-30 VDC/24 VAC
- RS485 and Ethernet communication protocols
Interface | USB |
Input Type | Potentiometer |
# of Inputs | 1 |
Output Type | 0 - 2 V DC, 0 - 5 V DC, 0 - 10 V DC, ±10 V DC, 0 - 5 mA, 0 - 20 mA, 4 - 20 mA, RS-485 |
Isolation | Yes |
Supply Power | 10 - 30 V DC, 10 - 24 V AC |
- Interfaces to 100 Ohm Platinum or 120 Ohm Nickel RTDs
- Linearizes RTD Signal
- Process Current Output
- 1500Vrms Transformer Isolation
- ANSI/IEEE C37.90.1 Transient Protection
- Input and Output Protected to 240VAC Continuous
- Up to 60V Loop Voltage
- 160dB CMR
Input Type | RTD |
# of Inputs | 1 |
Output Type | 4 - 20 mA |
Max Bandwidth | 3 Hz |
Isolation | Yes |
Supply Power | 12 - 60 V DC |
- Interfaces to Types J, K, T, E, R, S, B, and N Thermocouples
- Process Current Output
- 1500Vrms Transformer Isolation
- ANSI/IEEE C37.90.1 Transient Protection
- Input and Output Protected to 240VAC Continuous
- Up to 60V Loop Voltage
- 160dB CMR
- 85dB NMR at 60Hz, 80dB at 50Hz
Input Type | Thermocouple |
# of Inputs | 1 |
Output Type | 4 - 20 mA |
Max Bandwidth | 3 Hz |
Isolation | Yes |
Supply Power | 12 - 60 V DC |