SCMPB07, 8-Position Backpanel, High Density
- can accept any of the SCM5B analog modules
- 16 non-addressable analog IO signal channels
- Panel or DIN Rail Mounting Options
- 1500 Vrms Isolation
- CE Compliant
- 1-, 2-, 8-, 16-Position Backpanels
- 19-Inch Mounting Rack For Backpanels
- Multiplexed and Non-Multiplexed Backpanels
- Interface cables
- Module Evaluation Board
- Cable to Screw Terminal Interface Board
The SCMPB07 8-channel high-density backpanel can accept any of the SCM5B analog modules in any mixture. Its overall width is 5.5 inches (139.7mm) versus 10 inches (254mm) for the SCMPB05 and SCMPB06 8-channel backpanels. Separate analog signal paths are provided for each channel. Each channel provides four high-density screw terminals for field connections and two high-density screw terminals for host system connection. It also provides a jumper on each channel to optionally connect or isolate each module’s I/O common from other channel's I/O common and/or power common (Figure 16).
See Figure 11 for schematic.
SCMPB07 and SCMPB07-1 can be upgraded to DIN rail mounting. The following accessories are required for mounting one SCMPB07 or one SCMPB07-1 backpanel (for a visual example, reference SCMPB03/SCMPB04 page Figure 8):
Qty Model Description
2 SCMXBEFE Base element with snap foot
2 SCMXSE Side element
2 SCMXBE Base element without snap foot
12 SCMXVS Connection pins
Slots | 8 |
Input Type | Voltage |
Current | |
Strain Gauge | |
Thermocouple/RTD | |
Frequency | |
Analog Outputs | 8 |
Max Bandwidth | 11 kHz |
SCMPB07 | 8-Position Backpanel, High Density |
SCMPB07-1 | 8-channel backpanel without cold junction compensation circuits. |
SCMPB07-2 | 8-channel backpanel with DIN rail mounting hardware |
SCMPB07-3 | 8-channel backpanel without cold junction compensation circuits and with DIN rail mounting hardware. |
SCMPB01-07 Datasheet |
AN101 RMS_Voltage_Current App Note |
AN121 RiseTime vs BW App Note |
AN126 Tuning_Surge_Tank_Level_Control_Loops App Note |
AN128 RMS Revisited App Note |
AN129 Harmonics and utility costs App Note |
Signal Conditioning -Tutorial Tech Note |
Hysteresis Specifications Tech Note |
Faraday's Law of Induction Tech Note |
Data Acquisition Systems Accessories Tech Note |
Signal Conditioner Surge Withstand Capability Tech Note |
Signal-to-Noise Ratio, SNR Tech Note |
Signal Conditioning Measured vs Combinational Error Tech Note |
When Good Grounds Go Bad Tech Note |
Sample Test Report Tech Note |
- Narrow Bandwidth Voltage Input Module
- 1500 V Transformer Isolation
- Accuracy: ± 0.03%
- Module
- ANSI/IEEE C37.90.1 Transient Protection
- Input Protected to 240 V AC Continuous
Family | Dataforth 5B |
Input Type | ±10 mV DC, ±50 mV DC, ±100 mV DC, ±1 V DC |
# of Inputs | 1 |
Output Type | 0 - 5 V DC, 0 - 10 V DC, ±5 V DC, ±10 V DC |
Bandwidth | 4 Hz |
Isolation | Yes |
- Narrow Bandwidth Voltage Input Module
- 1500 V Transformer Isolation
- Accuracy: ± 0.03%
- Module
- ANSI/IEEE C37.90.1 Transient Protection
- Input Protected to 240 V AC Continuous
Family | Dataforth 5B |
Input Type | ±1 V DC, ±5 V DC, ±10 V DC, ±20 V DC, ±40 V DC |
# of Inputs | 1 |
Output Type | 0 - 5 V DC, 0 - 10 V DC, ±5 V DC, ±10 V DC |
Bandwidth | 4 Hz |
Isolation | Yes |
- Narrow Bandwidth Current Input Module
- 1500 V Transformer Isolation
- Accuracy: ± 0.03%
- Module
- ANSI/IEEE C37.90.1 Transient Protection
- Input Protected to 240 V AC Continuous
Family | Dataforth 5B |
Input Type | 0 - 20 mA, 4 - 20 mA |
# of Inputs | 1 |
Output Type | 0 - 5 V DC, 0 - 10 V DC |
Bandwidth | 4 Hz |
Isolation | Yes |
- True RMS Input Module
- 1500 V Transformer Isolation
- Accuracy: ± 0.03%
- Module
- ANSI/IEEE C37.90.1 Transient Protection
- Input Protected to 480 V AC & DC Max
Family | Dataforth 5B |
Input Type | 0 - 100 mV AC, 0 - 1 V AC, 0 - 10 V AC, 0 - 150 V AC, 0 - 300 V AC, 0 - 1 A AC, 0 - 5 A AC |
# of Inputs | 1 |
Output Type | 0 - 5 V DC, 0 - 10 V DC, 0 - 1 mA, 0 - 20 mA, 4 - 20 mA |
Isolation | Yes |
Supply Power | 5 V DC |
- Linearized 2- or 3-Wire RTD Input Module
- 1500 V Transformer Isolation
- Accuracy: ± 0.06°C to ± 0.36°C
- Module
- ANSI/IEEE C37.90.1 Transient Protection
- Input Protected to 240 V AC Continuous
Family | Dataforth 5B |
Input Type | RTD |
# of Inputs | 1 |
Output Type | 0 - 5 V DC, 0 - 10 V DC |
Bandwidth | 4 Hz |
Isolation | Yes |
- Non-Linearized Thermocouple Input Module
- 1500 V Transformer Isolation
- Accuracy: ± 0.03%
- Module
- ANSI/IEEE C37.90.1 Transient Protection
- Input Protected to 240 V AC Continuous
Family | Dataforth 5B |
Input Type | Thermocouple |
# of Inputs | 1 |
Output Type | 0 - 5 V DC, 0 - 10 V DC |
Bandwidth | 4 Hz |
Isolation | Yes |
- Strain Gauge Input Module
- 1500 V Transformer Isolation
- Accuracy: ± 0.03%
- Module
- ANSI/IEEE C37.90.1 Transient Protection
- Input Protected to 240 V AC Continuous
Family | Dataforth 5B |
Input Type | Strain Gauge |
# of Inputs | 1 |
Output Type | ±5 V DC, ±10 V DC |
Bandwidth | 10 kHz |
Excitation | 3.33 V DC, 10 V DC |
- Analog Output Module
- 1500 V Transformer Isolation
- Accuracy: ± 0.03%
- Module
- ANSI/IEEE C37.90.1 Transient Protection
- Input Protected to 240 V AC Continuous
Family | Dataforth 5B |
Input Type | 0 - 5 V DC, ±5 V DC, ±10 V DC, 0 - 20 mA |
# of Inputs | 1 |
Output Type | 0 - 20 mA, 4 - 20 mA, ±20 mA |
Bandwidth | 275 Hz, 400 Hz |
Isolation | Yes |
- Analog Input Module
- 1500 V Transformer Isolation
- Accuracy: ± 0.03%
- Module
- ANSI/IEEE C37.90.1 Transient Protection
- Input Protected to 240 V AC Continuous
Family | Dataforth 5B |
Input Type | ±1 V DC, ±5 V DC, ±10 V DC, ±20 V DC, ±40 V DC |
# of Inputs | 1 |
Output Type | 0 - 5 V DC, 0 - 10 V DC, ±5 V DC, ±10 V DC |
Bandwidth | 10 kHz |
Isolation | Yes |
- Frequency Input Module
- 1500 V Transformer Isolation
- Accuracy: ± 0.05%
- Module
- ANSI/IEEE C37.90.1 Transient Protection
- Input Protected to 240 V AC Continuous
Family | Dataforth 5B |
Input Type | Frequency |
# of Inputs | 1 |
Output Type | 0 - 5 V DC, 0 - 10 V DC |
Excitation | 5 V DC |
Isolation | Yes |