Loading...
A-Tech Instruments Ltd.
Français   |   Welcome. Please Register an Account or Login

SpeedSys 200, Transmitter & Overspeed Protection Controller

A high-integrity overspeed protection system for rotating machinery. The simple and robust design meets the latest safety standards, and features easy maintenance.
SpeedSys 200
SpeedSys 200
SpeedSys200
Features:
  • Overspeed, Underspeed and Acceleration Detection
  • Designed for versatility and scalable to the application
  • Suitable for API 670 and API 612 applications
  • Certified SIL 2 capability
  • Fast 8 ms system response time
  • 2 safety relays + 1 safety analog output per module
  • Suitable for all common sensor types
Manufacturer:  Istec International B.V.
Quote
Datasheet
Description
Specifications
Applications
Downloads
Related Products
Similar Products
SpeedSys 200 - Description

The SpeedSys 200 is a SIL-rated overspeed detection system for rotating machinery.

SpeedSys 200 - Specifications
InterfaceTCP/IP
Input Type±100 mV DC
±80 V DC
Frequency
# of Inputs1
Output Type0 - 10 V DC
Max Bandwidth10 kHz
Excitation20 V DC
Supply Power18 - 36 V DC
SpeedSys 200 - Applications

System that are well suited for Wind, Hydro and Steam Turbine Speed Monitoring and Alarming.

FT3000 overspeed protection system replacement

The FT3000 overspeed protection system, formerly supplied by the Jaquet Technology Group (now: TE Connectivity), has been discontinued by the manufacturer. The following is a replacement for the FT3000.

 

Bently Nevada BN3500 with Istec SpeedSys 200 Overspeed Detection System

When an overspeed situation occurs the system should trip the steam turbine to prevent potential damage and dangerous situations. Zero-speed was monitored to prevent the turning gear from starting soon. The turning gear can only be started, when the rotor has come to a complete stop, as this could otherwise damage the turning gear.

One of the relays of a SpeedSys 200 unit was configured to cover zero-speed monitoring, which was a function that was previously covered by the old BN3500 tachometer module.

The BN3500 was replaced with a 2oo3 SpeedSys 200 configuration. The DIN-rail assembly was engineered on-site and consists of the following components:

  • Two 24V power supplies
  • Three GSI 127 galvanic isolators
  • Three SpeedSys 200 modules, hardwired to form a 2oo3 voting structure
SpeedSys 200 - Downloads
SpeedSys 200 - Related Products
  • Differential Hall-Effect Sensor
  • Stainless Steel Housing (Model D12P)
  • Smooth Flange Mount (Model D12A)
  • Protection Class: IP67
  • Mounting Thread: M12 x 1
  • Connection: 4-pin M12 x 1 Connector (Model D12A)
  • Connection: 24 AWG PTFE-Insulated Leads (Model D12P)
Type
Hall Effect
Max Frequency
20 kHz
Mounting
10.8 mm OD flange
Connection
M12x1
Min Temperature
-40 °C
Max Temperature
125 °C
  • VRS Sensor
  • Stainless Steel Housing
  • Protection Class: IP67
  • Mounting Thread: M12 x 1
  • Connection: 4-pin M12 x 1 Connector (Model E12A)
  • Connection: 22 AWG Silicone-Insulated Leads (Model E12S)
  • Simple Installation
Type
Magnetic Pickup
Max Frequency
20 kHz
Mounting
M12x1
Connection
22 AWG Silicone-Insulated Leads,
M12x1
Min Temperature
-40 °C
Max Temperature
125 °C
  • VRS Sensor
  • Stainless Steel Housing
  • Protection Class: IP67
  • Mounting Thread: M16 x 1.5
  • Connection: 4-pin M12 x 1 Connector (Model E16A)
  • Connection: 22 AWG Silicone-Insulated Leads (Model E16S)
  • Connection: 2-pin MS3102A Connector (Model E16AM)
  • Simple Installation
Type
Magnetic Pickup
Max Frequency
20 kHz
Mounting
M16x1.5
Connection
22 AWG Silicone-Insulated Leads,
M12x1,
MS3102A
Min Temperature
-40 °C
Max Temperature
125 °C
SpeedSys 200 - Similar Products
  • Accepts 1 signal input from 3-wire voltage sensors (Hall-effect & proximity),
  • Accepts 2-wire voltage signals or digital input signals from encoders.
  • Dynamic monitoring, comparing chns, reverse rotation, creep and standstill.
  • Input Voltage Ranges from 20 mVrms to 80 Vrms
  • Input Frequency capable from 0.025 Hz up to 35 kHz (200kHz for Digital Pulse)
  • Two configurable relays (10 ms response time) for multiple speed functions
  • One highly accurate analog outputs (4-20 mA or optional 2 – 10 V)
  • One Frequency Signal Outputs, (open collector, max. 24 V, 100 ma)
Interface
TCP/IP,
RS-485
Input Type
20 milli Vrms,
0 - 10 V AC,
80 Vrms,
Frequency
# of Inputs
1
Output Type
2 - 10 V DC,
4 - 20 mA
Max Bandwidth
10 kHz
Excitation
24 V DC
Products    |    Applications    |    Services    |    Partners    |    About Us    |    Contact Us
© A-Tech Instruments Ltd.